AC
OUTPUT |
|
Output
voltage: |
120
VAC true sinewave output standard |
|
Output
rating: UPS |
1000
VA, 750 watts standard, |
|
Non-linear
load capacity: UPS |
Up
to 100% non-linear load capability w/o derating |
|
Output
voltage regulation: UPS |
± 3.0%
static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
|
Overload
surge capacity: UPS |
110%
for 10 minutes; 125% for 30 seconds |
|
Harmonic
distortion: UPS |
Less
than 5.0% into 100% non-linear load |
|
Output
frequency: UPS |
60
Hz or 50 Hz switch selectable
± 2.5% synchronized to utility
± 1.0% w/ utility not available |
|
Operational
status |
AC Input status, UPS
operational, UPS alarm, Battery level,
Low battery, Load level, Overload, Warm/Hot temperature,
Battleshort LEDs, +90 dB audible alarm w/audible on/off switch |
|
AC
INPUT |
|
Input
voltage selection: |
Autoranging
from nominal 115 VAC to 230 VAC |
|
Input
voltage tolerance: UPS |
+15%
-25%, or 85-140 and 170-280
@ full load without using battery, to 70 VAC @ 75% load |
|
Input
frequency: |
From
45 Hz to 70 Hz standard, optional to 440 Hz |
|
Input
power factor: |
Better
than 99% typically |
|
Input/output
isolation: |
up to 120 dB common mode, <1.0 ma leakage |
|
Input
transient suppression: |
Complies
with IEEE 587, UL 1449 and Mil Std 1399 |
|
Input
control/protection: |
Recessed 100 G shock rated circuit breaker (CB1)
Optional cold start switch available to turn on w/o AC present |
|
Input
power connections: |
One
IEC320 male, 3 pin |
|
INTERNAL
BATTERY |
|
Internal
battery type: |
Maintenance
free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
|
Internal battery life: |
Rated
for continuous service life of 5 years |
|
Internal battery
protection: |
Recessed 100 G shock rated circuit breaker (CB2) |
|
Internal
battery time: |
10+
minutes @ 750 watt load, 20+ minutes @ 50% |
|
Internal
battery recharge: |
Recharged
to nominal in <8 hours |
|
Internal
battery replacement: |
Hot
swap drawout/plug-in module from front of unit
<3 minutes to change battery modules |
|
Battery
expansion: |
Up
to 24 hours w/ optional Battery Expansion Modules |
|
DISTRIBUTION
PANEL |
|
Output
circuits: |
Four
AC outputs standard, several optional configurations |
|
Output
receptacles: AC output |
NEMA
5-15R, various
options |
|
MECHANICAL |
|
Dimensions
(H x D x W): UPS |
21.75 x 8.99 x 13.75 in (552 x
228 x 349 mm) |
Unit
weight:
UPS and Battery
UPS
only
Battery
Module only |
65
lb. (30 kg) with lift handles front and rear
37 lb. (17 kg) with lift handles front and rear
28 lb. (13 kg) with lift handle in front |
|
Audible
noise: |
Less
than 47 dB @ 5.0 ft., ANSI "A" scale |
|
Cooling
type: |
High
capacity, positive pressure, forced air |
|
Air
intake filter: |
Washable
metal filter media, others optional |
|
ENVIRONMENTAL |
|
Storage
temperature: |
-40° to
158° F ambient (-40° to 70° C) |
|
Operating
temperature: |
32° to
126° F ambient ( 0° to 52° C), lower/ higher optional |
|
Operating
humidity: |
0
to 95% relative humidity (non-condensing) |
|
Storage
elevation: |
Up
to 40,000 ft (12,192 m), higher optional |
|
Operating
elevation: |
Up
to 10,000 ft (3,048 m), higher optional |
|
STANDARDS |
|
United
States: |
Meets
UL-1778 standard for UPS equipment,
Meets MIL-STDs 1275, 167-1, 454, 810, 1399-300A
& MIL-S-901 |
|
Canada: |
CSA
C22.2 No. 107 UPS safety requirements |
|
EMI
Protection: |
EMI/RFI
FCC Part 15, Class A; EN55022 |
|
OPTIONAL
ACCESSORIES |
|
|
Cold Start, Alternate I/O
Configurations,
Battery Expansion,
Battery Charger/Conditioner,