Part
Number: ETI0001-2229
Rugged MilSpec 2000 VA
Rackmount Global UPS |
|
US
Navy / Raytheon SSDS (Ship Self Defense System)
Configuration
WorldPower™ Rugged MilSpec Rack Mount 2.0 kVA UPS
Autoranging Global Isolated Input Accepts 85-270 VAC, 46-70
Hz
Input PFC, Battleshort, Manual Bypass, Elapsed Time
Plus Front Access Hot Swappable Battery Module
Backward Compatible for Refitting Existing SSDS Systems

P/N: ETI0001-2229
Rugged MilSpec UPS Standard Front Panel Layout

P/N: ETI0001-2229 Rugged MilSpec UPS Standard Rear Panel
Layout
The field
proven WorldPower™ UPS line is ideally suited for
military, industrial, computer and telecommunications
applications requiring high reliability, rugged construction,
compact size and light weight design. These units are
equally suited for use in shipboard, airborne, vehicular,
field deployed or fixed locations with controlled or
uncontrolled environments. The ETI0001-2229 is The ETI0001-2229
is specifically designed for lightweight global power
by the US Navy as the power source for critical systems
because of the stringent performance and reliability
requirements.
The heavy-duty
chassis, occupying only 5.25”(3U) of rack space
while delivering up to 2000 VA of clean, uninterruptible
power. The rounded metal corners and rugged handles front
and rear, aid in safe handling. Internally, all major
components are well secured and electrically insulated
to prevent damage due to shock and vibration. These units
can be mounted horizontally or vertically. Optional heavy-duty
rack slides provide easy installation and removal of
the unit with full extension.
The internal
shielded input transformer provides galvanic isolation
with provisions for both domestic (115 VAC, CONUS) and
international (230 VAC, OCONUS) input voltages. The autoranging
input voltage selection allows inputting either 115 VAC
or 230 VAC without having to open the UPS enclosure.
Special EMI/RFI filters and input power factor correction
minimize both input current and harmonics. The unit also
operates as a frequency converter, taking 46-70 hertz
input and converting it to clean, uninterruptible 60
hertz power. Optionally, 46-440 hertz input as well either
50 or 400 hertz outputs are available.
The LED
arrays keep the operator informed as to the unit's status
including load and battery levels. The Elapsed Time Indicator
records the number of operational hours for records and
scheduling preventative maintenance of attached equipment.
The front panel also provides easy access to both the
AC Input and Battery Input fuses. Coupled with the adjacent
spare fuses, MTTR is reduced to less than 15 minutes.
The internal
intelligent thermal sensors provide two stage monitoring
of unit temperatures, with both local and remote Battleshort
override capability of thermal shutdown. Battleshort
can be engaged via the front panel control, via a remote
contact input or via a software command. When in Battleshort,
an audible alarm is sounded and an indicator is lit.
The high intensity audible alarm can be heard in high
noise environments and includes an audible enable/disable
switch.
All controls
and protective devices are brought to the front and rear
panels with critical switches or circuit breakers having
finger guards. Further, all front panel devices are recessed
to prevent damage or accidental operation. Clips on the
front panel hold spare fuses for ready access. The input
circuit breaker and the galvanic isolation transformer
all provide a double pole isolated source for shipboard
systems or overseas locations where phase references
and grounding are not consistent. The manual bypass feature
included is operated from the front panel. Even in the
bypass mode, the ETI0001-2229 still provides galvanic
isolation, transient surge protection and EMI/RFI filtering.
The ETI0001-2229 has
the added benefit of having a field replaceable battery
via front drawout battery module. The battery is a true
hot-swappable module and does not require going to bypass
like competing units. Even with this battery module removed,
this UPS can continue to operate as an electronic power
conditioner and frequency converter, providing clean,
well regulated, sinusoidal power to the load. The batteries
are maintenance free with immobilized electrolyte and
are constructed of flame retardant materials for added
safety. For more information, see the Battery
Technology section.
The rear
panel provides locking connectors for the input and output
power with various optional configurations available.
This unit draws air through the front air filter and
exhausts out the rear vent into the rack. This allows
the unit to be used in negative or neutral pressure racks.
For positive pressure racks, rear to front or rear to
side versions are available. A removable and washable
intake air filter and high capacity stainless steel ball
bearing fan provide added protection in both controlled
and hostile environments.
The two
status D shell connectors provide both a contact and
serial interface with optional computer
software providing loss of AC and low battery status
as well as remote shut down capability. See the Power
Distribution Units section for a listing of stand
alone PDUs. See the N5 Series for a version of
this UPS with an integrated PDU and remote control
Overall,
the PowerStation line is uniquely qualified for critical
shipboard, vehicle, airborne or land based systems combining
advanced modular design features with highly reliable
construction.
Technical Specifications:
ETI0001-2229
| AC
OUTPUT |
| Output
voltage: |
120
VAC true sinewave output standard |
| Output
rating: UPS |
2000
VA, 1500 watts standard
For
1000 VA, 750 watts, see ETI0001-2227
For
1000 VA, 750 watts, see ETI0001-2227AC (w/DC
Input)
For
1500 VA, 1125 watts, see ETI0001-2228 |
| Non-linear
load capacity: UPS |
Up
to 100% non-linear load capability w/o derating |
| Output
voltage regulation: UPS |
± 3.0%
static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
| Overload
surge capacity: UPS |
110%
for 10 minutes; 125% for 30 seconds |
| Harmonic
distortion: UPS |
Less
than 5.0% into 100% non-linear load |
| Output
frequency: UPS |
60
Hz ± 2.5% synchronized to utility
60 Hz ± 1.0% w/ utility not available |
| Operational
status |
AC
Input status, UPS operational, UPS alarm, Battery
level, Low battery, Load level, Overload, Warm temperature,
Hot temperature, Manual bypass and Battleshort LEDs,
Elapsed time hour meter
Alarm contacts for Loss of AC and Low Battery
+90 dB audible alarm with audible on/off switch
Asynchronous serial COM port |
| AC
INPUT |
| Input
voltage selection: |
Autoranging
from nominal 115 VAC to 230 VAC |
| Input
voltage tolerance: UPS |
+15%
-25%, or 85-135 and 170-270
@ full load without using battery, to 70 VAC @ 75%
load |
| Input
frequency: |
From
46 Hz to 70 Hz standard, optional to 440 Hz |
| Input
power factor: |
Better
than 99% typically |
| Input/output
isolation: |
2000
VA, up to 120 dB common mode, <1.0 ma leakage |
| Input
transient suppression: |
Complies
with IEEE 587, UL 1449 and Mil Std 1399 |
| Input
control/protection: |
Guarded
2 pole 100 G shock rated circuit breaker (CB1)
plus UPS input fuse (F2), spare fuse on front
Manual bypass switch to force bypass mode
Optional cold start switch available to turn on w/o
AC present |
| Input
power connections: |
One
MS 3102A-22-2P, 3 pin, locking |
| INTERNAL
BATTERY |
| Internal
battery type: |
Maintenance
free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
| Internal
battery life: |
Rated
for continuous service life of 5 years |
| Internal
battery protection: |
Front
panel mounted fuse (F1), spare fuse on front |
| Internal
battery time: |
6+
minutes @ 1500 watts,10+ minutes @ 1000 watt load |
| Internal
battery recharge: |
Recharged
to nominal in <8 hours |
| Internal
battery replacement: |
Hot
swap drawout/plug-in module from front of unit
<3 minutes to change battery modules |
| Battery
expansion: |
Up
to 24 hours w/ optional Battery Expansion Modules |
| DISTRIBUTION
PANEL |
| Output
circuits: |
Six
AC outputs standard, several optional configurations |
| Output
control: |
Only
via CB1; optional remote control panel w/switches
available |
| Output
receptacles: AC output |
NEMA
5-15R with locking cable bales standard,
various options |
| MECHANICAL |
| Dimensions
(H x D x W): UPS |
5.25
(3U) x 23.5 x 19.0 in (133 x 597 x 483 mm) |
| Rack
Slide Mount Patterns: |
Jonathan,
General Devices patterns standard, others optional |
| Alternate
Mounting Options: |
Table,
Wall, Floor, Portable, Horizontal/Vertical |
Unit
weight:
UPS and Battery
UPS only
Battery Module only |
105 lb. (48 kg) with lift handles front and rear
65 lb. (30 kg) with lift handles front and rear
40 lb. (18 kg) with lift handle in front |
| Audible
noise: |
Less
than 47 dB @ 5.0 ft., ANSI "A" scale |
| Cooling
type: |
High
capacity, negative pressure, forced air |
| Cooling
air direction: |
Front
intake, exhaust to rear, others optional |
| Air
intake filter: |
Washable
metal filter media, others optional |
| ENVIRONMENTAL |
| Storage
temperature: |
-40° to
158° F ambient (-40° to 70° C) |
| Operating
temperature: |
32° to
126° F ambient ( 0° to 52° C), lower/ higher optional |
| Operating
humidity: |
0
to 95% relative humidity (non-condensing) |
| Storage
elevation: |
Up
to 40,000 ft (12,192 m), higher optional |
| Operating
elevation: |
Up
to 10,000 ft (3,048 m), higher optional |
| STANDARDS |
| United
States: |
Meets
UL-1778 standard for UPS equipment,
Meets MIL-STDs 1275, 167-1, 454, 810, 1399-300A &
MIL-S-901 |
| Canada: |
CSA
C22.2 No. 107 UPS safety requirements |
| EMI
Protection: |
EMI/RFI
FCC Part 15, Class A; EN55022; MIL STD 461 |
| OPTIONAL
ACCESSORIES |
| |
Emergency
Power Off, Elapsed Time Meter, Cold Start, Alternate
I/O Configurations, Dual Source Input, Battery
Expansion, Battery
Charger/Conditioner, Power
Distribution Units, Software
Interface, 10BaseT Ethernet SNMP/HTTP port, Transport
Cases, Batteryless Operation |
This
page was last modified on: