HOME INVERTERS GENERATORS CONDITIONERS UPS PDU SOLAR ECU FUEL CELLS CABLES Contact Us Links

P/N: ETI0018-1625
DC/AC Power Inverter
2500 Watts
12 VDC In
200/220/240 VAC Out


Tactical Briefcase and
Transit Case Inverters:

Features

True sinewave output (THD < 3%)
Power On-Off Remote Control
Input & Output fully isolated
Load control cooling fan
Advanced microprocessor
Output frequency 50/60 Hz selectable
Low power saving mode to conserve energy
Built-in transfer switch & AC circuit breaker
ROF (Remote Override Function) or ignition lockout function option
Speed up transfer time & synchronized operation with utility AC source
Input polarity reverse/ under voltage / over voltage protections
Output short circuit/ overload / over temperature protections
Tri-color indicators display input, output level & failure status
e-13/ CE /FCC approved
 


Universal Mount Inverters-c/w Transfer Switch

Rugged Universal Mount Sinewave Inverter

Model Numbers:
ETI0018-1125
ETI0018-1025
ETI0018-1225
ETI0018-1625
ETI0018-1525
ETI0018-1725
      AC Output
AC Voltage
   100 / 110 / 120 VAC    220 / 230 / 240 VAC
Rated Power
      2500 W
Surge Power
      5000 W
Waveform
      True sinewave (THD < 3%)
Frequency
      50 / 60 Hz selectable by DIP switch
AC Regulation
      +/- 3%
Power Factor Allowed
      COS -90° ~ COS +90°
Standard Receptacles
      HARDWARE
LED Indicator
      Input voltage level, output load level & fault status
      DC Input
No Load Current Draw
 2.62A  1.53A  0.72A  2.32A  1.15A  0.68A
Stand-By Current Draw
 0.60A  0.30A  0.20A  0.60A  0.30A  0.15A
DC Voltage
 12 VDC   24 VDC  48 VDC  12 VDC  24 VDC  48 VDC
Voltage Range
 10.5~15.0 VDC  21~30 VDC  42~60 VDC  10.5~15.0 VDC  21~30 VDC  42~60 VDC
Efficiency (Typ.)
 88.0%  91.0%  92.0%  90.0%  93.0%  94.0%
Fuse
 40A x 10  20A x 10  20A x 6  40A x 10  20A x 10  20A x 6
Circuit Breaker
   35 A    15 A
Synchronous AC Transfer
      Yes
Transfer Switch
      25 A    15 A
Transfer Time
      Inverter to utility AC:8~10 msec.: Utility AC to inverter:12~14 msec
Remote Control Unit
      CR6 / CR8 optional
      Protection
Low Battery Alarm
 11 VDC  22 VDC  44 VDC  11 VDC  22 VDC  44 VDC
Low Battery Shutdown
 10.5 VDC  21.0 VDC  42.0 VDC  10.5 VDC  21.0 VDC  42.0 VDC
Over load
      Shut off output voltage, re-power on to recover
Over Voltage
 15.3 VDC  30.6 VDC  61.2 VDC  15.3 VDC  30.6 VDC  61.2 VDC
Over Temperature
      Shut off output voltage, recovers automatically after temperature goes down 
Output Short
      Shut off output voltage, re-power on to recover
Battery Polarity
      By fuse opening
      Environmental
Working Temperature
      0 ~ +40° C
Working Humidity
      20% ~ 90% RH non-condensing
Storage Temp. Humidity
      -30° C ~ +70° C / -22° F ~ +158° F / 10~95%
      Standards
Safety Standards
   Meets UL458    
Isolation Resistance
   I/P ~ O/P: 100M Ohms / 500 VDC   
EMI & Radiation
   Compliance to FCC Class A    Compliance to EN55022 Class A
EMS Immunity
             Compliance to EN61000-3 -2, 3
LVD
   Compliance to EN60950-1
e-MARK
   Compliance to e-13 * 72/245/EEC, 95/54/EC
      Mechanical
Dimensions
      463 x 332 x 115 MM (L x W x H)
Packaging
      12 kgs; 1 set / 13 kgs / CARTON
Cooling
      Load controlled cooling fan

This page was last modified on: February 6, 2008

Information Request Form

Select the items that apply, and then let us know how to contact you.

Send product literature
Have an engineer contact me
Have a salesperson contact me
I prefer to be contacted by Email;   Telephone;  Fax;  Regular mail
My requirement is immediate;  1-3 months;  3-6 months;  Future

Name  
Title  
Company  
Address  
Email  
Phone  
Fax  
To Better Help You, Please
Describe Your
Requirements
 

Click here to visit our main site.



Copyright © 2000-2008 Energy Technologies, Inc.- All Worldwide Rights Reserved.
911Power™, TacticalPower®, TacticalGenerator® and  MilitaryPower® are registered trademarks of Energy Technologies, Inc.
TacticalInverter™, TacticalUPS™, TacticalBriefcase™, TacticalFuelCells™ and TacticalSolar™
are trademarks of Energy Technologies, Inc. Send comments or questions regarding this site to: webmaster@tacticalpower.com